RV Furnace Won't Ignite: Find Where It Stops
Every time you turn up the heat, an RV furnace goes through the same steps: fan, airflow check, spark, flame. Where it stops tells you what to check — and when to stop and call a technician.

If you smell propane: leave the RV, close the tank valve if it's safe to do so, and call 911 from a safe distance.
What the furnace does when you turn up the heat
From Suburban's user manual and Camping World's furnace troubleshooting guide (October 2026). Dometic (Atwood) furnaces follow the same order.
The thermostat calls for heat
It must be set to Furnace or Heat and above room temperature.
The control board checks the battery
If the 12-volt battery is too low, the furnace stays in standby until there is enough power.
The fan starts
Not instantly: Suburban's manual says to allow about 30 seconds.
The sail switch confirms airflow
It is a small switch that closes only when the fan moves enough air. If it doesn't close within about 30 seconds, the furnace locks out.
Spark and gas
The igniter clicks and the gas valve opens. Suburban: allow 30 seconds for the burner to light after the fan starts. There is no pilot light — don't try to light the burner by hand.
Three tries, then lockout
After three failed tries the gas valve stays closed and the fan runs a few more minutes to clear the furnace, then stops until you reset it at the thermostat.
Nothing happens at all: no fan, no click
The furnace never starts. Look for 12-volt power first — the fan and the controls run on the battery even though the burner uses propane.
- Thermostat
Set it to Furnace or Heat, a few degrees above room temperature. Replace its batteries if it has them.
- Battery disconnect switch
Make sure the RV's battery switch is on. Do the ceiling lights and the refrigerator controls work? If not, the problem is 12-volt power, not the furnace.
- Low battery
Plug into shore power or run the generator for a while, then try again. A weak battery keeps the furnace in standby.
- Furnace fuse or breaker
Check the furnace fuse in the 12-volt panel. Some Dometic furnaces have a 15-amp breaker in the main panel that can trip when the furnace starts.
- The furnace's own switch
Some furnaces have their own on/off switch. On Dometic furnaces with an access door it is inside the door; on doorless models it is usually on top of the housing against the wall. Suburban SF and SH furnaces have a switch on the gas valve. With the switch off, no gas reaches the burner.
The fan runs, then stops — no click
The fan starts but the igniter never clicks. The board did not get the airflow signal from the sail switch.
- Battery voltage
A weak battery turns the fan too slowly to close the sail switch. Charge the battery or plug in and try again.
- Return air
Move bags, bedding and boxes away from the furnace's return grille and open the floor registers. Suburban's manual: remove any restrictions to the return air openings.
- No booster fans in the ducts
Suburban says duct boosters make the sail switch work erratically. Remove any that were added.
Don't bend or bypass the sail switch. It is one of the furnace's safety controls; a technician tests it and replaces it with the right part for your model.
The fan runs and it clicks, but there's no flame
Airflow is fine and the igniter is sparking, but the burner doesn't catch. Start with the propane.
- Tank valve fully open
Open the valve on the propane tank all the way. Suburban's manual: never operate the furnace with a valve partially closed.
- Propane in the tank
Weigh the tank or read its gauge. On a cold night a tank can run out without warning.
- Test with the stove
Light a stove burner. If it burns steadily, propane is reaching the RV. If you just changed or refilled a tank, light the stove first and then try the furnace.
- Reset once
Turn the thermostat off and back on. If the burner still doesn't light after three attempts, stop — Suburban's manual says not to keep cycling the thermostat to force ignition.
It lights, then goes out — or lights late
- Shut it down
Suburban's manual: shut the furnace down immediately and call for service if it cycles erratically or is slow to ignite.
- Look at the outside vent
Wasp and mud dauber nests block furnace vents. Clear what you can reach from outside — don't push anything metal inside. Never cover the vent with a screen: Suburban says screens become restricted and make the furnace unsafe. If a door of the RV can cover the vent when open, keep it closed while the furnace runs.
- Soot on the vent
Soot on the outside vent means incomplete burning. Shut the furnace down and don't use it until a technician has checked it.
- Vents and ducts
A furnace that heats for a few minutes and shuts off is often overheating: blocked return air, closed registers or crushed ducts trip its limit switch.
Dometic furnaces: read the status light
Dometic (Atwood Hydro Flame) furnaces show faults with a red status light on the control board. On furnaces with an access door you see it inside the door; on doorless models the return-air grille has to come off. Some newer systems also show codes on a compatible digital thermostat.
- Steady light — control board failure. Hard lockout.
- 1 flash, then a pause — limit switch or airflow problem. Check the vents and the return grille.
- 2 flashes — flame sense fault. Hard lockout.
- 3 flashes — ignition lockout: three tries without flame. Check the propane, then reset.
A hard lockout needs a reset at the thermostat or the furnace's power switch. Suburban's user manual describes the lockout but no light codes. Source: Camping World, “Suburban and Dometic RV Furnace Troubleshooting and Repair”, October 2026.

Propane work in Texas
In Texas, work on an RV's propane system — gas lines, the regulator, gas valves and burners — is done by technicians licensed by the Railroad Commission of Texas. Before propane work starts, ask the technician for their license number. You can look it up on the Railroad Commission website.
Furnace ignition questions
What are the common causes of an RV furnace not igniting?
An empty or partly closed propane tank, a weak 12-volt battery, a blocked return grille, or the furnace's own switch left off. Past those checks: the sail switch, the igniter and its electrode, the control board or the gas valve — those are for a technician.
How do I reset an RV furnace?
Turn the thermostat off, wait a minute and turn it back on. On Dometic furnaces you can also turn the furnace's power switch off and on. Reset once — if the burner still doesn't light after three attempts, call a technician.
Where is the sail switch on an RV furnace?
Inside the furnace, by the blower. On Dometic 79 and 80 series furnaces the furnace has to come out of the RV to reach it; larger models with an outer door can be serviced in place. It is a safety control — have a technician test and replace it.
Why does my RV furnace click but not light?
The igniter is sparking, so power and airflow are fine. Usually the gas isn't reaching the burner: a closed or empty tank, or a line that hasn't filled yet after a tank change — light the stove first. If the stove lights and the furnace still doesn't, a technician checks the gas pressure, the electrode and the gas valve.
Is it safe to keep trying to light the furnace?
No. Suburban's manual says to stop after three attempts and call for service, and to shut the furnace down right away if it lights late or cycles erratically. If you smell propane, leave the RV first.
Request a technician
Tell us what's wrong and where your RV is. We send your request to independent mobile RV technicians who serve that part of DFW.